Performance/Safety Related Concern for Kidde-Fenwal, Inc. “Low Pressure CO2” Nozzle Cover Assembly (Frangible Disc) Issue
- Type of Notification: Product Safety Notification
- FM Approval Status: FM Approved
FM Approvals has been made aware by Kidde-Fenwal Inc. of a potential safety related issue involving the Kidde Fire Systems Low Pressure Carbon Dioxide Extinguishing System. The root cause of the concern is related to a quality control issue.
Company Identity: Kidde-Fenwal, Inc.
Address: 400 Main Street
Ashland, MA 01721
USA
Contact Information: Technical Services at kidde_techsupport@carrier.com
FM Approval Status: FM Approved
Hazard Involved: The product in question is any Kidde Fire Systems Low Pressure Carbon Dioxide (LPCO2) Extinguishing System that includes a Frangible Sealing Disc, P/N WK-260885-000, which is used in the Flange and Cover Assembly for Type V Nozzles, P/N 81-844492-000. It has been determined that the frangible disc may not rupture at the minimum nozzle pressure of 150 psi, which could result in the system not discharging into the protected hazard.
USING THIS PRODUCT?
Antonio Pires
Norwood, MA, United States
+1 (1) 781-255-4825