FM Approvals has been made aware by Siemens AG of a potential safety related hazard caused by a supplier quality issue in the SIMATIC ET 200SP 4x 24..230VAC/2A ST (6ES7 132-6FD00-0BB1) DQ and the SIMATIC S7-1500 PS 60W 24/48/60 VDC HF (6ES7505-0RB00-0AB0) Modules.
Company Identity: Siemens AG – DI FA
Product Identity:
ET 200SP 4x 120..230VAC/2A ST (6ES7 132-6FD00-0BB1)
S7-1500 PS 60W 24/48/60 VDC HF (6ES7505-0RB00-0AB0)
Nameplate Data: FM Approvals Certificate Numbers as follows:
6ES7 132-6FD00-0BB1: FM16US0053X & FM16CA0029X
6ES7 505-0RB00-0AB0: FM24US0007X & FM24CA0002X*
Description: DQ Modules for the ET 200SP and S7-1500 Systems
FM Approval Status: FM Approved
Hazard Involved: ET 200SP 4x 120..230VAC/2A ST (6ES7 132-6FD00-0BB1) Module - The affected DQ modules do not comply with the normative requirements regarding safe electrical separation and explosion protection. As a result, contact with dangerous voltages, sparking or overheating can occur in individual cases when installed. This can result in damage to equipment and personal injury.
S7-1500 PS 60W 24/48/60 VDC HF (6ES7505-0RB00-0AB0) Module - The affected PS modules do not comply with the normative requirements regarding explosion protection. As a result, sparking can occur in individual cases when installed. This can result in damage to equipment and personal injury.