Micropack (Engineering) Ltd has notified FM Approvals of a potential safety concern involving their Model FS300 and FDS301 Optical Flame Detectors and FDS301 Flame Simulators manufactured between July 2012 and July 2019.
Company Identity: Micropack (Engineering) Ltd
Address: School Hill, Portlethen, Aberdeen, AB12 4RR, United Kingdom
Contact Information: Customer Support:
Phone Number +44 1224 784055.
Email Info@micropack.co.uk
Product Identity:
Micropack (Engineering) Ltd Models FDS300 and FDS301 Optical Flame Detectors and Model FS301 Flame Simulator
Consilium Marine & Safety AB Models CD-F 300 and CD-F 301 Optical Flame Detectors and Model CD-FS 301 Flame Simulator
Dräger Safety UK Ltd Models Flame 3000 and Flame 5000 Optical Flame Detectors and Model FS5000 Flame Simulator
Description:
he Models FDS300, CD-F 300 and Flame 3000 Optical Flame Detectors are monochrome imaging-based flame detector.
The Models FDS301, CD-F 301 and Flame 5000 Optical Flame Detectors are color imaging-based flame detector.
The Models FS301, CD-FS 301 and FS5000 Flame Simulator are used to test the correct operation of the Flame Detectors.
Nameplate Data:
Micropack (Engineering) Ltd Models FDS300 and FDS301
Consilium Marine & Safety AB Models CD-F 300 and CD-F 301
Dräger Safety UK Ltd Models Flame 3000 and Flame 5000 Flame Detectors
US
Class I, Division 1, Groups B, C and D T4
Class I, Zone 1, AEx db IIC T4
Type 4X / IP66
Ta = -60°C to +85°C (-76°F to +185°F)
Canada
Class I, Division 1, Groups B, C and D T4
Class I, Zone 1, Ex db IIC T4
Type 4X / IP66
Ta = -60°C to +85°C (-76°F to +185°F)
ATEX
II 2 G Ex db IIC T4 Ta=-60°C to +85ºC IP66
IECEx
Ex db IIC T4 Ta=-60°C to +85ºC IP66
Micropack (Engineering) Ltd Model FS301
Consilium Marine & Safety AB Model CD-FS 301
Dräger Safety UK Ltd Model FS5000 Flame Simulators
ATEX
II 2 (2) G Ex db [op is T6 Gb]
IIC T6 Gb Ta = -10°C to +50°C IP66
FM Approval Status: FM Approved
Hazard Involved: Micropack (Engineering) Ltd shipped non-conforming Micropack (Engineering) Ltd Models FDS300 and FDS301 Optical Flame Detectors, Consilium Marine & Safety AB Models CD-F 300 and CD-F 301 Optical Flame Detectors, Dräger Safety UK Ltd Models Flame 3000 and Flame 5000 Optical Flame Detectors, Micropack (Engineering) Ltd Model FS301 Flame Simulator, Consilium Marine & Safety AB Model CD-FS 301 Flame Simulator, and Dräger Safety UK Ltd Model FS5000 Flame Simulators manufactured between July 2012 and July 2019.
Due to a dimensional issue with the glass window in the assembly of the flame detectors and flame simulator, the resulting flame-path gaps do not meet the requirements of IEC 60079-1 for IIC applications and FM 3615 Class 1 DIV 1 Groups B, C and D applications. This is a safety related non-conformance that could present a dangerous situation in certain applications of the product.
Micropack (Engineering) Ltd, Consilium Marine & Safety AB and Dräger Safety UK Ltd are reaching out to all users to notify them of this situation (see attached Product Safety Notifications).